# Three-phase current: P = √3 × VL × IL - Source-Date (SAST): 2023-11-08 15:50 - From/To: Eric → support - Dest: both - Review-after: 2027-02-28 - Status: current - Source: company email (Archives/Internal Affairs), 2023-11-08 ## Facts - Three-phase: **P (kW) = √3 × VL × IL**. √3 ≈ 1.732. **VL** (line voltage) is **380 V** in most SA installs. **IL** is current per line. - Example: 7.5 kW vacuum pump → 7500 = 1.732 × 380 × IL → **IL ≈ 11.4 A**. - Circuit-breaker minimum: **CNC machines × 1.25**; **motors × 1.5** (so 11.4 A motor → about 17 A minimum). - Worked load example: 5.5 kW-spindle CNC router with cooler ≈ **8 kW** whole machine, plus **7.5 kW** vacuum pump, plus **3 kW** dust collector — size the breaker from the summed kW using the formula and the CNC/motor factors above.